Conductor sizing

Voltage drop calculator

Estimate voltage drop, percent drop, and end voltage for any run — copper or aluminum, single- or three-phase — and size the conductor to NEC's 3% branch and 5% combined guidance.

Phase

Voltage drop

Enter a run to estimate voltage drop.

Estimated results
Voltage drop
Percent drop
Voltage at load
Resistance used
NEC 3% branch NEC 5% total
Estimate only — not a substitute for a licensed electrician. Based on NEC Ch.9 Table 8 DC resistance. Does not model ampacity, temperature derating, power factor, or continuous-load factors. Verify against the current NEC and your local code / AHJ.

Method

The estimate uses the single-conductor formula Vdrop = K × length × current × (R ÷ 1000). K is 2 for single-phase and √3 (about 1.732) for three-phase. R is the conductor's DC resistance in ohms per 1000 ft, taken from NEC Chapter 9, Table 8 for uncoated copper and aluminum. Percent drop is the drop divided by the source voltage.

NEC 3% / 5% guidance

The NEC suggests (informational note, not a hard rule) a branch circuit stay at or below 3% and the feeder plus branch stay at or below 5%. The calculator flags both. When a run exceeds 3%, it suggests the thinnest conductor that brings it back under 3% so you don't over-buy copper.

Based on NEC Ch.9 Table 8 (DC resistance, ~75°C, uncoated conductors).

FAQ

How is voltage drop calculated?

Voltage drop = K × length (ft) × current (A) × (R ÷ 1000), where K is 2 for single-phase or √3 for three-phase, and R is the conductor's DC resistance in ohms per 1000 ft. Percent drop is the voltage drop divided by the source voltage, times 100.

What voltage drop does the NEC allow?

The NEC's informational notes recommend keeping a branch circuit at or below 3% and the feeder plus branch combined at or below 5%. These are recommendations (FPN), not enforceable rules, but most designers and inspectors treat 3% as the practical target.

Does copper or aluminum drop more voltage?

For the same size, aluminum has higher resistance than copper, so it drops more voltage. To carry the same load over the same distance with a similar drop, aluminum usually needs to be one or two sizes larger than copper.

What does this calculator not include?

It estimates voltage drop only, using NEC Chapter 9 Table 8 DC resistance. It does not size for ampacity, temperature derating, conduit fill, power factor, or continuous-load factors, and it is not a substitute for a licensed electrician or your local code (AHJ).

Estimate only, based on NEC Chapter 9 Table 8 DC resistance. This is not a substitute for a licensed electrician or your local code (AHJ). It does not fully model ampacity, temperature derating, power factor, or continuous-load factors. Always verify against the current NEC and local code before wiring. Based on NEC Ch.9 Table 8.