Voltage drop scenario

Wire size for 50 amps at 200 feet

At 240 V single-phase, copper 4 AWG keeps a 50 amps load at about 2.57% drop over 200 feet — within the NEC 3% branch target. Adjust material, voltage, or phase below.

Phase

Voltage drop

Enter a run to estimate voltage drop.

Estimated results
Voltage drop
Percent drop
Voltage at load
Resistance used
NEC 3% branch NEC 5% total
Estimate only — not a substitute for a licensed electrician. Based on NEC Ch.9 Table 8 DC resistance. Does not model ampacity, temperature derating, power factor, or continuous-load factors. Verify against the current NEC and your local code / AHJ.

50 amps at 200 feet: the short answer

At 240 V single-phase over 200 feet, a 50 amps load needs copper 4 AWG to stay near 2.57% — inside the NEC 3% branch-circuit target. For comparison, copper 12 AWG would drop about 38.60 V (16.08%) on the same run.

Before you pull wire

This is a voltage-drop estimate only. The conductor must also meet ampacity, temperature derating, and overcurrent rules — use the larger of the voltage-drop size and the ampacity size. Aluminum of the same size drops more, so it usually needs to go up one or two sizes. Always confirm with a licensed electrician and your local code (AHJ).

Sized for voltage drop using NEC Ch.9 Table 8 (DC resistance).

FAQ

What wire size do I need for 50 amps at 200 feet?

For voltage drop at 240 V single-phase, copper 4 AWG keeps a 50 amps load near 2.57% over 200 feet, meeting the NEC 3% branch guidance. Ampacity, derating, and local code may require a different size — confirm with a licensed electrician.

How much voltage drop does 50 amps over 200 feet have?

On a baseline copper 12 AWG at 240 V single-phase, 50 amps over 200 feet drops about 38.60 V (16.08%). Larger conductors drop less; the calculator shows the exact figure for any size.

Is this voltage-drop sizing the same as ampacity sizing?

No. This page sizes for voltage drop only, using NEC Chapter 9 Table 8 DC resistance. The conductor must also satisfy ampacity, temperature derating, and overcurrent-protection rules. Use the larger of the voltage-drop size and the ampacity size, and verify with your local code (AHJ).

Estimate only, based on NEC Chapter 9 Table 8 DC resistance. Not a substitute for a licensed electrician or your local code (AHJ). Voltage-drop sizing does not replace ampacity, temperature derating, power factor, or continuous-load checks. Verify against the current NEC and local code before wiring. Based on NEC Ch.9 Table 8.